|
No Room Air Blower
The room air blower in all England's stove works pellet
units is controlled by the circuit board. this blower does not start
until the unit has reached operating temperature. use the following
steps to determine why the room air blower is not running.
Click
Here for Downloadable Instruction Sheets
1. Is there a fire in the unit? the unit must be at
operating temperature to turn on the blower.
2. What is the "blower speed" set at? The room air blower runs
very slowly in its lowest settings and does not run at all in setting 0.
3. Does the stove shut off completely at 20-30 minutes from starting?
The circuit board's heat sensor must read enough temperature during
startup to engage the "run" mode of the stove, if this temperature is
not read by the sensor, not only will the room air blower not come on
the stove will shut off. If this is the case, check the heat sensor
wires , make sure that the sensor is tight against the firewall and that
it is plugged in to the control board. If this is all correct replace
the heat sensor (part number
PU-CBHS ).
If the problem is not solved by using the steps above, remove the
rear access panel, locate the blower and follow its wires back to the
control board. unplug the two room air blower wires from the control
board plug them into the terminals for another component such as the
lower auger motor. and turn the unit on , the room air blower should
start if the blower itself is good. If the blower still does not start
the blower should be replaced.
|